Operating Principle
The displacer level transmitter (or any other buoyancy level
transmitter) uses the effect of buoyancy. When the displacer is immersed in the
process fluid, this buoyancy effect will make the displacer lighter than the
non immersed displacer. This change of displacer weight is then detected by the
sensor (whether use torque tube or LVDT) and then translated as a fluid level.
Before we calibrate the displacer level transmitter, we must
aware that the transmitter has been set at factory as per process fluid
Specific Gravity (SG), while we will use water as the calibration fluid. When
the displacer is operated by using actual process fluid, it will show 4 mA at
low level (the displacer is not immersed) and 20 mA at high level (the
displacer is fully immersed). Thus before we calibrate the transmitter, we need
to calculate the equivalence of this buoyancy effect if we use water as the
test fluid instead of using actual process fluid (which is in practice are very
difficult to get).
Non-Interface
Displacer Level Transmitter Calibration Procedure
1. Calculate the
equivalence water level
Zero level =
displacer not immersed (no need certain adjustment)
Calculate the high
level using this equation:
(Process Fluid
Operating SG / Water SG)*Transmitter Level Range
2. Set up the
Displacer Level Transmitter to column or temporary support as shown in the
calibration setup file below.
3. Fill the level
transmitter chamber with water up to the centre of the lower part flange of the
LIT cage as a zero level.
4. By using handheld
HART communicator set this level as zero level (see also in the LCD display of
the transmitter, it should show zero level).
5. Read the mA output
of the transmitter by using a multimeter. Adjust (if any) through the HART
communicator so that the output of the transmitter (on multimeter) is 4 mA.
6. Fill the level
transmitter chamber with water up to the calculated equivalence high level
above.
7. By using handheld
HART communicator set this level as high level (see also in the LCD display of
the transmitter, it should show high level).
8. Read the mA output
of the transmitter by using a multimeter. Adjust (if any) through the HART
communicator so that the output of the transmitter (on multimeter) is 20 mA.
Interface
Displacer Level Transmitter Calibration Procedure
1. Calculate the
equivalence water level
Calculate zero level
using this equation:
(Lighter Process
Fluid Operating SG / Water SG)*Transmitter Level Range
Calculate the high
level using this equation:
(Heavier Process
Fluid Operating SG / Water SG)*Transmitter Level Range
2. Set up the
Displacer Level Transmitter to column or temporary support as shown in the
calibration setup file below.
3. Fill the level
transmitter chamber with water up to the calculated equivalence zero level
above.
4. By using handheld
HART communicator set this level as zero level (see also in the LCD display of
the transmitter, it should show zero level).
5. Read the mA output
of the transmitter by using a multimeter. Adjust (if any) through the HART
communicator so that the output of the transmitter (on multimeter) is 4 mA.
6. Fill the level
transmitter chamber with water up to the calculated equivalence high level
above.
7. By using handheld
HART communicator set this level as high level (see also in the LCD display of
the transmitter, it should show high level).
8. Read the mA output
of the transmitter by using a multimeter. Adjust (if any) through the HART
communicator so that the output of the transmitter (on multimeter) is 20 mA.
Example of
equivalence water level calculation:
Level Transmitter
Level Range = 38 inch
Water SG = 1
Process Fluid SG =
0.84
Equivalence high
level using water = (0.84/1)*38 = 31.92 inch
It means the
displacer should show 20 mA while we fill the chamber up to 31.92 inch with
water fluid as test fluid.
Interface Application
Level Transmitter
Level Range = 38 inch
Water SG = 1
Lighter Process Fluid
SG = 0.695
Heavier Process Fluid
SG = 0.994
Equivalence zero
level using water = (0.695/1)*38 = 26.41 inch
It means the
displacer should show 4 mA while we fill the chamber up to 26.41 inch with
water fluid as test fluid.
Equivalence high
level using water = (0.994/1)*38 = 37.772 inch
It means the
displacer should show 20 mA while we fill the chamber up to 37.772 inch with
water fluid as test fluid.
Typical tools
required:
1.24 VDC power supply
2.Multimeter digital
3.Water Supply
Connection
4.HART communicator
5.Screwdriver set
6.Wrench set
Note: This typical
maintenance procedure is just an illustration of how to regularly service a
displacer level transmitter for academic purpose only. This typical procedure
shall not be used as day to day operation guidance. The vendor specific
maintenance manual shall be used in detail.
My cousin recommended this blog and she was totally right keep up the fantastic work!
ReplyDeleteTorque Calibration
You can find more information on Instrumentation here
ReplyDeletehttp://www.instrumentationtools.com/
Thanks
Bharadwaj
That's very important calibration and it is very clear.
ReplyDeleteThanks a lot.
I really learned something.
Help alot🇲🇾
ReplyDelete